菜单
  

    Design in addition to meet the indoor air temperature, humidity and speed requirements, more important is to meet the comfort requirements. Combined with the characteristics of buildings, each floor rooms adopt fan-coil unit plus fresh air system.
    The main content of the design include:
    (1)the air-conditioning cooling load calculation
    This design uses Hongye load calculation software for load calculation. In the process of load calculation, I must be to set the building location, meteorological parameters and other basic information in first; secondly, I according the construction drawings to calculate the area of air conditioning room and set the meteorological parameters of each air-conditioned room area, and then choose the building maintenance structure, sets the indoor density, equipment power ,lighting power According to the features of the building.
    Because of the corridor, kitchen, restroom and shower area is small and the occupancy is small, they has a good ventilation. From the economic into consideration these areas are not installed air conditioning, no mechanical ventilation
    The building cooling load is 83.57Kw by the load calculation, air conditioning room area is 482.03 m ², cooling load index is 173W/ m ².
        (2) the choice of the form of air conditioning system
        Air conditioning area of the Australian company office building belonging to the small area of the building, the primaries of all air system and fan-coil unit plus fresh air system, the advantages and disadvantages of the two systems, according to the characteristics of the building, the building room area is lesser, for flexible control and convenient management, final selection of fan-coil plus fresh air air conditioning system.
        (3) the air handling process
        This system adopts the summer fresh air to the state of the indoor isenthalpic line, after fresh air and fan coil air supply mixture into the room
    (4) the design of air conditioning system
        1、air system design
        This design adopts air sent back, tuyere choice as a diffuser to supply air outlet.
        The building of the air-conditioned room area is lesser, rooms require a separate regulation, therefore adopts a fan-coil unit plus fresh air system, fresh air duct independent new air.
        Fresh air system is provided with a single, independent supply indoor, outdoor weather changes can be carried out with the regulation, indoor parameter to that fresh air treatment, do not assume room load, assure indoor humidity and fresh air requirement. This scheme can improve the system of regulation and the flexibility of the operation, and into the fan coil water temperature can be appropriately increased, water condensation phenomenon can be improved.
        2、exhaust design
        The air conditioning room because in the ground, and are outside the window, the window can use natural ventilation. A layer of the restroom, two layer, three layer corridor restroom, kitchen, located in the south of the south wall, and have a large enough area of the window, can be naturally ventilated good, so that these areas do not exhaust design. But considering the bathroom winter may be closed, if not done in exhaust design, which will make it very boring, so in the two bathroom three layers in each with one type of exhaust fan the same.
        (5) the design of air conditioning water system
    According to the characteristic of the building, and through the comparison of various water system, I decided to closed DRS, dual control, single pump system in this design.
       (6) the selection of the main equipment
    The type of fan coil is choosed by the cooling load it bears . The type of the fresh air unit is choosed by cold load of fresh air unit. Chiller type according to the total amount of refrigeration. Chilled water pumps and cooling water pumps models are selected according to their head and flow. Cooling tower type is selected according to the flow of cooling water. Expansion tank type is selected according to the effective volume.
  1. 上一篇:五层现浇钢筋混凝土框架结构和建筑设计+CAD图纸
  2. 下一篇:300吨土建式冷藏库设计+CAD图纸
  1. 6层科大办公楼框架结构设计+CAD图纸

  2. 某会议培训中心建筑四层框架结构设计+图纸

  3. 合肥市华海混凝土厂房四...

  4. 中国驻某国大使馆四层框架结构设计+图纸

  5. 四层会议培训中心办公楼...

  6. 西安市联通公司大楼给排...

  7. 长江办公楼工程量清单及招标控制价编制

  8. 高警觉工作人群的元情绪...

  9. g-C3N4光催化剂的制备和光催化性能研究

  10. 上市公司股权结构对经营绩效的影响研究

  11. 中国传统元素在游戏角色...

  12. NFC协议物理层的软件实现+文献综述

  13. C++最短路径算法研究和程序设计

  14. 浅析中国古代宗法制度

  15. 江苏省某高中学生体质现状的调查研究

  16. 巴金《激流三部曲》高觉新的悲剧命运

  17. 现代简约美式风格在室内家装中的运用

  

About

优尔论文网手机版...

主页:http://www.youerw.com

关闭返回