菜单
  

    more exhaust fans must operate during economizer periodsand the greater airflow required to remove the increased heat load ismore sensitive to the increase in static pressure from duct use.Because of the high fan energy use, a significant improvement inefficiency is observed in the Economizer Plus scenario inwhich thereis a larger temperature difference between the supply and return air.Even though the supply air temperature ismaintained at the Baselinedesign setpoint, cooling energy use is nearly eliminated in themilderclimate regions for mid-tier data centers with the Economizer Plusdesign.The use of water-cooled chillers for the cooling system in enter-prise data centers provides for the most efficient calculated Baselinedesign PUE values and these results are nearly identical across allclimate regions. Outside wetbulb temperature, which varies lesswith outside air conditions than drybulb temperature, limits theefficiency ofwater-cooled systems. In Dallas and Richmond, Baselinedesign PUE values for the enterprise data center are even lower thanthe respective server room and localized data center PUE values forthe Economizer design. The high airflow required for enterprise datacenters causes significant fan energy demand that is furtherincreased by the addition ofmultiple exhaust fans in the Economizerscenario. Without increasing the difference in temperature set-points, this high fan energy demand partially offsets the largeenergy savings gained from reduced chiller operation duringincreased hours of economizer use. However, in the Economizer Plusdesign, the high efficiency of the water-cooled chiller-based coolingsystem means that the increased chiller activity that results fromonly raising the return air temperature (and maintaining the supplyair temperature at the Baseline setting) is small compared to the fan energy savings associated with lower required airflow rates. WithPUE values of 1.30e1.46, depending on climate, the energy efficiencyof the Economizer Plus scenario for enterprise data centers is the bestof all the cases evaluated in this study.In general, relaxing humidity restrictions in the Economizer andEconomizer Plus scenarios improved PUE values by allowing for anincrease in the hours of economizer operation. However, whenapplying the Baseline temperature settings with a DX coolingsystem, completely removing the humidity restrictions (1e100%RH) resulted in increased cooling energy demand in more humidclimates (Chicago, Richmond, Dallas). Cooling during high humidityperiods, when the outside temperature is below the return airdrybulb setpoint and upper dewpoint economizer lockout, canresult in significant latent cooling demand. The increase in coolingenergy associated with relaxed humidity restrictions did not occurafter shifting from DX cooling to chiller systems in the larger datacenters and did not occur in any of the cooling systems when thetemperature setpoints were raised in the Economizer Plus scenario.The PUE results fromFig.1 are applied to the IT energy estimatesin Table 1 to provide the US national data center energy use esti-mates presented in Fig. 2. The 2008 data center energy use estimateof 69 billion kWh would decline to 63 billion kWh when applyingthe Baseline PUE values calculated in this study rather than theuniform PUE of 2.0 as is commonly assumed to apply. The 10%difference in annual energy use may be largely attributable to theidealized airflow and control system characterization used in themodel, suggesting that improved operation of current non-econo-mizer data centers (e.g., better airflow management andcommissioned control sequences) might yield substantial energysavings. The Economizer scenario, inwhich economizers are used inall data centers except for server closets while maintaining theBaseline temperature and humidity restrictions, reduces the annualnational data center energy use estimate to 57 billion kWh.Enterprise data centers provide the greatest savings in the Econo-mizer scenario, owing to significant PUE improvements and thelarge IT energy use attributed to this data center space type. TheEconomizer Plus scenario yields an additional savings of 4 billionkWh/year (to 53 billion kWh/y nationwide) from operating theeconomizers under relaxed humidity and temperature conditionsin local, mid-tier, and enterprise data centers. Although enterprisedata centers represent the largest portion of energy demand,
  1. 上一篇:氟伐他汀抑制昆虫保幼激素合成英文文献和中文翻译
  2. 下一篇:注塑模具的设计与热分析英文文献和中文翻译
  1. 会计矿业环境估值方法英文文献和中文翻译

  2. 会计师事务所任期与审计...

  3. ADO.NET结构与概述英文文献和中文翻译

  4. 信息系统开发与数据库开...

  5. 机器人学入门力学与控制英文文献和中文翻译

  6. 园林植物景观的园林绿化...

  7. 船舶与海洋结构物水动力...

  8. NFC协议物理层的软件实现+文献综述

  9. 江苏省某高中学生体质现状的调查研究

  10. 上市公司股权结构对经营绩效的影响研究

  11. 巴金《激流三部曲》高觉新的悲剧命运

  12. g-C3N4光催化剂的制备和光催化性能研究

  13. C++最短路径算法研究和程序设计

  14. 高警觉工作人群的元情绪...

  15. 中国传统元素在游戏角色...

  16. 现代简约美式风格在室内家装中的运用

  17. 浅析中国古代宗法制度

  

About

优尔论文网手机版...

主页:http://www.youerw.com

关闭返回