菜单
  

    个计算单元的保护面积均为 424.67m2
    ,各计算单元最小需配灭火级别为 4A,选用手提式
    灭火器,其最大保护距离为 20m。确定灭火器设置点为 3个,每个灭火器设置点的最小
    需配灭火级别为3A。
    选用既能扑灭B类火灾,也能扑灭 A类火灾,也适用于扑救 E类火灾的手提式磷酸
    铵盐干粉灭火器,型号为 MF/ABC5。每个灭火器设置点选配 2具5kg手提式 MF/ABC5
    灭火器,每层共配置6具。 机械加压送风系统设计:在防烟楼梯间设置机械加压送风系统,楼梯间的加压送风口
    每隔两三层设置1个,而在前室则每层设 1个。 设计送风量为19861m3/h,本设计中取风速为 6m/s,风口面积为0.5m2,选择
    850mm×600mm 自垂式百叶风口。  
    关键词:高层建筑;消防安全现状;消火栓;灭火器;加压送风
    A current situation analysis of fire safety and fire protection
    design of high-rise residential
    General description of the design: the object of this design is a high-rise residential buildings,
    located in Henan Province, building area of 22224.86m2
    . The highest elevation of the ground is
    78.8with 26 on ground floors and 2 underground floors.
    The building with the shear wall structure, seismic crack is 6 degrees, and the first
    underground layer is antiaircraft basement. Each layer of a total of 8 households, pided into A,
    B two kinds of apartment layout. The design consists of two buildings close to each other but
    not connected, showing symmetric structure of high-rise residential tower.
    The task of this design is to complete the analysis of the present status of the high-rise civil
    building fire safety and fire protection system design and related calculations. Specific contents
    include:  the design about general plan of architecture’ fire protection design, the flat fire
    protection design of the building, safety evacuation design, fire hydrant system design, fire
    extinguisher configuration design, mechanical pressure air supply systems design.
    Through the analysis of the current situation of fire safety to this design objects, I found
    that there are a lot of fire safety problems on the high-rise building. The main fire safety
    problems are as followed. There are defects of the fire protection design, and the design can’t
    meet with the design specifications. Fire facilities are not complete, with improper maintenance.
    These problems bring  security hidden danger to people's life, making people's lives and
    property threatened. For the high-rise residential building fire protection problems  the related
    departments should  strengthen the rectification measures, at the same time, should start with
    fire control design, dismantling and correcting errors in the unreasonable fire control design. In
    this way, it can prevent fire accident from the source and ensure that fire safety.
    The design about general plan of architecture’ fire protection design: The design object
    belongs to the first class of high-rise buildings, and fire resistance rating is the first level. The
    minimum fireproof distance with neighboring buildings is 15m, comply with the requirements
    of the specification. The ring of fire lane is around the building, setting away from the wall at
    5.00m, and the width is 4.00m, and Set the fire up rise venues On the back of the building.
    The flat fire protection design of the building: Each floor of each layer are set to 1 fire
    partition, floor refractory limit is 1.5h.
    Safety evacuation design: safe evacuation route design for  the room - corridor -  the front
    room  -  stairwells, piding  evacuation  secure partition, namely:  safety  corridors  for the first
    partition,  the front room  is the second  security zones, Stairwell  to  the third  security partition
  1. 上一篇:公寓项目建设成本控制技术研究
  2. 下一篇:混凝土简支梁按施工工艺设计+图纸
  1. 旧城改造存在的问题及对策研究

  2. 江科大实验楼BIM综合运用...

  3. 高层商务综合楼的建筑设计

  4. 人民是国家安全的什么和管理者

  5. 五层青年旅社的框架建筑结构设计+图纸

  6. 大学实验楼BIM综合运用基于BIM的技术标的编制

  7. BIM的综合楼工程商务标编制+CAD图纸

  8. 浅析中国古代宗法制度

  9. 中国传统元素在游戏角色...

  10. 现代简约美式风格在室内家装中的运用

  11. C++最短路径算法研究和程序设计

  12. g-C3N4光催化剂的制备和光催化性能研究

  13. 上市公司股权结构对经营绩效的影响研究

  14. 巴金《激流三部曲》高觉新的悲剧命运

  15. 江苏省某高中学生体质现状的调查研究

  16. 高警觉工作人群的元情绪...

  17. NFC协议物理层的软件实现+文献综述

  

About

优尔论文网手机版...

主页:http://www.youerw.com

关闭返回